Calculate how many BTUs you need for an air conditioner, a heater or a room. Adjust for size, ceiling height, climate, insulation, sunlight and occupancy — and see exactly which of them is driving the number.
Cooling and heating are calculated separately — a heating load is not a cooling load reused. Start with the quick estimate; open Improve this estimate when you can describe the building itself.
Estimated cooling load: 10,500 BTU/hr— that is the calculation. 12,000 BTU/hr is the nearest appropriate common capacity class at or above it, which is a different number and is chosen, not computed.
Estimate quality: Basic This is the quick estimate: a room-size model with named adjustments. Open Improve this estimate to describe the building itself.
The advanced estimate gives 8,300 BTU/hr for this room — 21% lower than the figure above. The advanced estimate works from the actual walls, glazing, roof, floor and air-change rate instead of generalized room factors, and is normally the more tailored of the two. It is showing a default building description until you fill some of it in.
Where your BTUs come from
Load component
BTU/hr
Share
Relative size
Room and envelope
8,000
77%
Climate
960
9%
Windows and sun
896
9%
Equipment
0
0%
Occupants
600
6%
Estimated cooling load
10,456
100%
Largest driver: room and envelope, at 77% of the total.
What is driving this result
Sunny is one of the reasons this estimate is above what floor area alone would suggest. Shading that glass is usually cheaper than buying capacity to fight it.
Cross-check against the ENERGY STAR chart
The ENERGY STAR figure is a recommended equipment capacity, not a calculated thermal load. It is compared here against this page’s recommended nominal size, which is the same kind of quantity. The estimated load is shown separately and is expected to sit below both.
For a 400 up to 450 ft² room.
Figure
BTU/hr
What it is
ENERGY STAR capacity
10,000
A recommended room air conditioner size
This page, nominal size
12,000
The same kind of quantity, 20% higher
This page, estimated load
10,456
A calculated thermal load. Expected to sit below both — it carries no sizing margin
The two are different instruments and are not expected to land on the same figure. The published chart is a room-unit selection table calculated on an 8 ft ceiling, and it carries no adjustment beyond shade, sun, extra occupants and a kitchen. Here, the difference comes from:
the chart carries no climate adjustment and this room is in a warm climate
sun exposure is set to sunny
there are 3 occupants rather than the chart’s baseline of 2
the chart is banded, so one capacity covers every room from 400 to 450 ft² — a 13% spread in floor area answered by a single figure
a published capacity is rounded up to a unit you can actually buy, so it carries a sizing margin a calculated load does not
See how this result was calculated
Base room load+8,000 BTU/hr400 ft² × 20 BTU/hr per ft² at an 8 ft ceilingrunning total 8,000 BTU/hr
Ceiling height+0 BTU/hr8.0 ft ceiling is 0% more air than the 8 ft basisrunning total 8,000 BTU/hr
Climate+960 BTU/hrWarm climate, ×1.12running total 8,960 BTU/hr
Insulation+0 BTU/hrAverage insulation, ×1.00running total 8,960 BTU/hr
Sun exposure+896 BTU/hrSunny, ×1.10running total 9,856 BTU/hr
Room use+0 BTU/hrLiving room, ×1.00running total 9,856 BTU/hr
Occupants+600 BTU/hr3 people; ENERGY STAR adds 600 BTU/hr for each person above 2running total 10,456 BTU/hr
Estimated load 10,456 BTU/hr, displayed as 10,500 BTU/hr because this model does not know a room to the last BTU. The recommendation step then selects the smallest capacity class at or above it: 12,000 BTU/hr, leaving 1,544 BTU/hr of headroom.
Conditions actually used
Indoor target
75°F
Outdoor design
95°F
Floor area
400 ft²
Ceiling height
8.0 ft
Conditioned volume
3,200 ft³
Engine
btu-calculator v1.0.0 · coefficients v1.0.0
Assumptions this result rests on
Exterior walls not entered — assumed 2, a corner room.
Window area not entered — assumed 15% of the exterior wall area, about 48 ft².
Glazing not identified — treated as plain double glazing (U 0.49, SHGC 0.62).
Equipment heat not entered — the living room default of 300 W is used.
What is above the ceiling was left on the default — treated as a vented attic above.
What is below the floor was left on the default — treated as an unheated space below.
Indoor target 75°F, outdoor design temperature 95°F.
Quick estimate: a room-size model with named adjustments, including ENERGY STAR’s own occupancy and kitchen rules.
See what changes your BTU requirement
Each row below is this same room recalculated with one thing changed, through the identical engine — not a rule of thumb about what improvements usually do.
Change
Estimated load
Difference
Nominal size
As entered now
10,500 BTU/hr
—
12,000 BTU/hr
Improve insulation to good
9,450 BTU/hr
−986 (−9.4%)
10,000 BTU/hr changes the class
Shade the windows
8,650 BTU/hr
−1,792 (−17.1%)
9,000 BTU/hr changes the class
Glazing and air-sealing scenarios appear once you open Improve this estimate: the quick model has no window U-factor and no air-change term for them to act on.
Cooling and heating
Load breakdown shown
Every coefficient published
How many BTUs do I need?
Enough to remove the heat that actually enters the room, or to replace the heat that actually leaves it. That is a different quantity for every room, which is why the honest answer starts with a question rather than a number.
For a rough anchor: an ordinary 400 square foot room with a standard 8 ft ceiling, in a moderate climate with average insulation and average sun and two people in it, comes out at 8,000 BTU/hr of cooling on this model, pointing at a 8,000 BTU/hr class. Move that same room somewhere hot, raise the ceiling, take the shade away and add three more people and it is nearly double.
Three things decide how far the answer moves: how much air there is (floor area times ceiling height, not floor area alone), how easily heat crosses the envelope (insulation, glazing, what is above and below, how draughty it is) and how much heat is already inside or arriving through the glass (sunlight, people, equipment). The calculator above walks through all three; the load breakdown shows which one is dominating your room.
BTU per square foot
“BTU per square foot” is a rule of thumb, not a constant. About 20 BTU/hr per square foot is the figure the category is built on, and it is where this model starts — but square footage alone cannot account for ceiling height, insulation, windows, sun exposure, occupancy or outdoor temperature, and every one of those moves the rate.
The same 400 ft² room, with one thing changed at a time. Generated by the calculator on this page, not typed in separately.
Condition
BTU/hr per ft²
Estimated load
Nominal size
Baseline: moderate climate, average insulation, average sun, 8 ft ceiling
20.0
8,000
8,000
Cool climate
17.0
6,800
8,000
Moderate climate
20.0
8,000
8,000
Warm climate
22.4
8,960
9,000
Hot climate
25.0
10,000
10,000
Very hot climate
27.6
11,040
12,000
Poor insulation
23.0
9,200
10,000
Average insulation
20.0
8,000
8,000
Good insulation
18.0
7,200
8,000
Excellent insulation
16.4
6,560
8,000
Mostly shaded
18.0
7,200
8,000
Average
20.0
8,000
8,000
Sunny
22.0
8,800
9,000
Strong afternoon sun
23.6
9,440
10,000
10 ft ceiling
25.0
10,000
10,000
Five occupants
24.5
9,800
10,000
Across those cases alone the implied rate runs from 16.4 to 27.6 BTU/hr per square foot — a 1.7-fold spread on one unchanged floor area.
Even the published ENERGY STAR chart does not imply a constant. Read across its own rows, the capacity per square foot at the bottom of each band falls from about 50 BTU/hr per ft² at the small end to about 17 at the large end. A small room carries a fixed overhead that a large one spreads out.
The published chart, in full
ENERGY STAR’s published room air conditioner cooling capacity chart, reproduced in full. The third column is arithmetic on the publisher’s own figures, not a published value.
Area to be cooled (sq ft)
Capacity needed (BTU/hr)
Implied BTU/hr per ft² at the low end
100 up to 150
5,000
50.0
150 up to 250
6,000
40.0
250 up to 300
7,000
28.0
300 up to 350
8,000
26.7
350 up to 400
9,000
25.7
400 up to 450
10,000
25.0
450 up to 550
12,000
26.7
550 up to 700
14,000
25.5
700 up to 1,000
18,000
25.7
1,000 up to 1,200
21,000
21.0
1,200 up to 1,400
23,000
19.2
1,400 up to 1,500
24,000
17.1
1,500 up to 2,000
30,000
20.0
2,000 up to 2,500
34,000
17.0
The capacities are calculated based on an 8-foot ceiling. If you have higher ceilings, you may want to select a room air conditioner with a higher CADR.
The publisher then lists four adjustments, quoted here exactly as written:
If the room is heavily shaded, reduce capacity by 10 percent.
If the room is very sunny, increase capacity by 10 percent.
If more than two people regularly occupy the room, add 600 BTUs for each additional person.
If the unit is used in a kitchen, increase capacity by 4,000 BTUs.
Source: ENERGY STAR, U.S. Environmental Protection Agency — Room Air Conditioners — cooling capacity chart and sizing adjustments. Retrieved August 19, 2026. This chart sizes ROOM air conditioners for a single room. It is not a whole-house load calculation, it carries no climate, insulation, window or air-leakage adjustment beyond the four listed above, and the publisher states no BTU-per-square-foot constant anywhere — the implied rate varies from about 33 BTU/hr per ft² at the small end of the chart to about 17 at the large end.
BTU calculator by room size
Starting estimates for common room sizes, generated by the calculator above at a fixed set of assumptions and shown next to what the published ENERGY STAR chart gives for the same area. The ENERGY STAR figure is a recommended equipment capacity, so the column to read it against is Common AC size. Setting it beside the estimated load instead would put a product size next to a thermal load and read the chart’s built-in sizing margin as a disagreement. Where the two capacities still differ, the reason is one of the things the chart does not ask about, or the width of the band it answers.
Starting estimates by room area. Assumptions: an 8 ft ceiling, a moderate climate, average insulation, average sun exposure, two occupants and ordinary room use. Change any one of those and the figure moves — that is the point of the calculator above. Read the last column against Common AC size, not against the estimated load: both of those are capacities, and the load is not.
Room area
Estimated load
Common AC size
BTU/hr per ft²
ENERGY STAR capacity
100 sq ft
2,000 BTU/hr
5,000 BTU/hr
20.0
5,000 BTU/hr
150 sq ft
3,000 BTU/hr
5,000 BTU/hr
20.0
6,000 BTU/hr
200 sq ft
4,000 BTU/hr
5,000 BTU/hr
20.0
6,000 BTU/hr
250 sq ft
5,000 BTU/hr
5,000 BTU/hr
20.0
7,000 BTU/hr
300 sq ft
6,000 BTU/hr
6,000 BTU/hr
20.0
8,000 BTU/hr
400 sq ft
8,000 BTU/hr
8,000 BTU/hr
20.0
10,000 BTU/hr
500 sq ft
10,000 BTU/hr
10,000 BTU/hr
20.0
12,000 BTU/hr
600 sq ft
12,000 BTU/hr
12,000 BTU/hr
20.0
14,000 BTU/hr
750 sq ft
15,000 BTU/hr
15,000 BTU/hr
20.0
18,000 BTU/hr
1,000 sq ft
20,000 BTU/hr
20,000 BTU/hr
20.0
21,000 BTU/hr
1,200 sq ft
24,000 BTU/hr
24,000 BTU/hr
20.0
23,000 BTU/hr
1,500 sq ft
30,000 BTU/hr
30,000 BTU/hr
20.0
30,000 BTU/hr
Use these to sanity-check a quote or narrow a shortlist. Do not use them instead of the calculator: every row assumes a standard ceiling, average insulation, moderate exposure, two occupants and a moderate climate, and changing any one of those is worth more than moving up a row.
How to calculate BTU for an air conditioner
The short version, and the one every “BTU calculator” on the web implements:
BTU/hr ≈ floor area (ft²) × BTU per ft²
It is a shortcut, and it is worth knowing exactly what it leaves out. It assumes an 8 ft ceiling, an average climate, an average envelope, average glass and two people. Four of those five are usually wrong for the room you are actually standing in.
A more useful calculation considers
Room volume, not floor area — a 10 ft ceiling is 25% more air to cool than an 8 ft one.
The outdoor design temperature and the indoor temperature you actually want.
Insulation, as a U-factor on each surface rather than as an adjective.
Window area, glazing type and which way it faces — usually the largest single cooling load in the room.
How many exterior walls the room has, and whether there is conditioned space above and below it.
Occupancy, and the equipment that runs during the hottest part of the day.
Air leakage, as air changes per hour against the room’s volume.
That is what Improve this estimate switches the calculator over to. Instead of one multiplier chain it computes each path heat takes into the room and adds them up:
Q_cooling = Σ(U × A × ΔT) + solar through glass + occupants + equipment + air leakage
where the solar term is window area × an orientation-dependent peak irradiance × the glazing SHGC × a shading factor, and the air leakage term is 0.075 lb/ft³ × 0.24 BTU/lb·°F × air changes per hour × room volume × ΔT.
How to calculate heating BTUs
Heating is a cleaner calculation than cooling, because there is no sun and no useful internal gain to argue about. Everything comes down to a temperature difference across a surface:
Q_heating = Σ(U × A × ΔT) + air leakage, where ΔT = indoor target − outdoor design temperature
The ΔT is the whole story, and it is exactly what a per-square-foot heating rule of thumb hides. Holding 70°F against a 35°F night is a 35°F difference; holding the same temperature against -10°F is 80°F — more than twice the load for exactly the same room.
Two rules this page follows that simple heating calculators usually do not:
No credit is taken for internal gains. Body heat, appliances and sunlight all help on an average day and are all absent on the design night the system has to cope with. Sizing on them is how a heating system ends up unable to reach setpoint in January.
Heating BTUs are not cooling BTUs. The same room can need far more heating capacity than cooling capacity, or the reverse. Switch the toggle at the top of the page and the whole calculation changes, not just a coefficient.
Note also that a furnace is often rated by input rather than output. A 80,000 BTU/hr furnace at 80% efficiency delivers about 64,000 BTU/hr into the house. This page estimates the heat the room needs — the output — so compare it against an output rating, not an input one.
What affects the BTU requirement?
In rough order of how much they usually move the number for a single room:
Sunlight through glass. In the advanced model this is frequently the largest single line. West-facing glass is the worst case at 165 BTU/hr per square foot of glass at peak, against 45 for north-facing.
The temperature difference. Every transmission term is directly proportional to it, so the design temperature you size against matters as much as the building does.
Insulation. Between the poorest and best grades this model uses, the wall U-factor changes by a factor of 6.3 and the roof by 15.0.
Ceiling height. It scales the conditioned volume directly, and it is the input people most often forget to change.
What is above the ceiling. A sunlit attic runs about 15°F above outdoor air; an uninsulated roof in full sun, about 25°F above. That is why top-floor rooms are the hard ones.
Air leakage. Between a tight room and a very draughty one this model moves the air-change rate from 0.35 to 1.60 per hour — a factor of 4.6 on that whole term.
People and equipment. Each occupant adds about 450 BTU/hr of cooling load, and every watt of equipment running becomes 3.41 BTU/hr of heat.
What “good insulation” actually means
“Good insulation” is not a measurement, so it is worth anchoring it to something that is. ENERGY STAR publishes recommended R-values by United States climate zone, based on the 2021 IECC:
ENERGY STAR recommended home insulation R-values — what a well-insulated assembly should reach, by United States climate zone. The first attic column applies where the attic is uninsulated; the second applies where three to four inches of insulation are already present.
Climate zone
Attic, if uninsulated
Attic, if 3–4 in already
Floor
Zone 1
R30
R25
R13
Zone 2
R49
R38
R13
Zone 3
R49
R38
R19
Zone 4A and 4B
R60
R49
R19
Zone 6, 5, and 4C
R60
R49
R30
Zone 7 and 8
R60
R49
R38
This guidance is based on the 2021 International Energy Conservation Code (IECC) Residential Provisions Chapter 4 Table R402.1.3. See Code for more detailed guidance. Source: ENERGY STAR, U.S. Environmental Protection Agency — Recommended Home Insulation R-Values. Retrieved August 19, 2026. These are recommended R-values for insulation work, not measured assembly U-factors for an existing building, and they are retrofit guidance for wood-framed housing in United States climate zones. They tell you what a well-insulated assembly should reach; they do not tell you what your wall is today.
Those are the figures to aim for. What the calculator needs is what your room is today, so the four grades it offers translate as follows — and these R-values are CalcDomain’s own model parameters, not the publisher’s:
What each insulation grade means inside this model.
Grade
Describes
Wall
Roof
Floor
Poor
Little or no cavity insulation — an uninsulated wood-frame assembly or an older solid wall.
R4
R3
R4
Average
Insulated cavities but no continuous exterior insulation — a typical existing home.
R10
R20
R13
Good
A code-compliant retrofit: full cavity insulation plus continuous sheathing, attic at about R30.
R17
R30
R20
Excellent
High-performance envelope: deep attic insulation at R49–R60 and a well-insulated wall assembly.
R25
R50
R30
What room size can my AC cool?
The same model, run backwards. Enter a capacity and it solves for the area whose estimated load equals it — under three different sets of room conditions, because a single square-footage answer would be the same mistake this page exists to avoid.
A 12,000 BTU/hr unit covers roughly 342–741 sq ft depending on the room, and an 18,000 BTU/hr unit roughly 531–1,111 sq ft. Here is the whole ladder:
How much room each common capacity can serve, at an 8 ft ceiling. The typical column is an average room; the range spans a shaded well-insulated room with two people at one end and a hot, poorly insulated, sunny room with four at the other.
Unit capacity
Tons
Typical room
Range across conditions
5,000 BTU/hr
0.42
250 sq ft
120–309 sq ft
6,000 BTU/hr
0.50
300 sq ft
152–370 sq ft
8,000 BTU/hr
0.67
400 sq ft
215–494 sq ft
10,000 BTU/hr
0.83
500 sq ft
278–617 sq ft
12,000 BTU/hr
1.00
600 sq ft
342–741 sq ft
14,000 BTU/hr
1.17
700 sq ft
405–864 sq ft
18,000 BTU/hr
1.50
900 sq ft
531–1,111 sq ft
24,000 BTU/hr
2.00
1,200 sq ft
721–1,481 sq ft
36,000 BTU/hr
3.00
1,800 sq ft
1,100–2,222 sq ft
BTU to tons
For equipment capacity, one ton of refrigeration is defined as exactly 12,000 BTU per hour. It is a definition rather than a measurement, and it says nothing about how much the equipment weighs — the name is a historical hangover from the rate of cooling produced by a ton of melting ice in a day.
tons = BTU/hr ÷ 12,000 · BTU/hr = tons × 12,000
The common sizes
Tons
BTU/hr
0.50
6,000
0.75
9,000
1.00
12,000
1.50
18,000
2.00
24,000
2.50
30,000
3.00
36,000
4.00
48,000
5.00
60,000
BTU to watts and kW
A BTU per hour and a watt are both units of power, so converting between them is exact. Using the International Table BTU of 1055.05585262 joules:
1 BTU/hr = 0.293071 W · 1 kW = 3,412.142 BTU/hr
This is a capacity conversion, not an electricity bill
A 12,000 BTU/hr air conditioner does not draw 3.52 kW from the wall. That figure is the rate at which it moves heat out of the room, not the electrical power it consumes to do it. A heat pump or air conditioner moves several units of heat for each unit of electricity, so actual consumption is a fraction of the capacity — how big a fraction is what SEER, EER and COP ratings describe. Converting capacity to watts tells you nothing about running cost on its own.
What is a BTU?
A British thermal unit is an amount of energy: approximately the energy needed to raise the temperature of one pound of water by one degree Fahrenheit, under defined conditions. Precisely, the International Table BTU used for equipment ratings is defined as 1055.05585262 joules.
A BTU per hour is something different — a rate at which energy moves, which is to say a power, in the same family as the watt. That distinction is the one thing worth taking away from this page:
When somebody says “a 12,000 BTU air conditioner”, they mean a unit with a capacity of about 12,000 BTU per hour. The trade drops the “per hour” in speech; the rating never does.
When a gas appliance is labelled in BTU, that is usually also a per-hour input rate.
An energy bill measures energy, not a rate — which is why it is billed in kilowatt-hours or therms rather than in watts.
Everything this calculator produces is a rate, in BTU per hour, and every label on the page says so.
BTU calculation examples
Three rooms, run through the calculator above at build time. Every figure here is produced by the same engine, so if a coefficient changes these change with it.
Example 1 — sizing an air conditioner for a bedroom
A 12 × 12 ft bedroom with a standard ceiling, in a moderate climate, average insulation, average sun, two people.
Where that load comes from. Computed live by the same engine the calculator runs, so these figures cannot drift from the tool above.
Component
BTU/hr
Share
Room and envelope
4,030
47%
Windows and sun
1,911
22%
Air leakage
2,621
31%
Two 400 sq ft rooms can need very different capacities
Room A
10 ft ceiling · poor insulation · unshaded west-facing afternoon sun · five people
18,800 BTU/hr
Nearest class 20,000 BTU/hr · 1.67 tons · 46.9 BTU/hr per ft²
Room B
8 ft ceiling · excellent insulation · shaded · two people
5,000 BTU/hr
Nearest class 6,000 BTU/hr · 0.50 tons · 12.5 BTU/hr per ft²
Both rooms are 400 square feet. Room A needs about 3.7× the cooling capacity of Room B — 13,744 BTU/hr more — and lands 8 capacity classes higher. Any calculator that answers “how many BTUs for 400 square feet?” with a single number is answering a question nobody actually has.
Why the right BTU size matters
If it is too small
It runs for longer to reach the setpoint, and on a genuine design day it may not reach it at all.
Temperature control is slower, and recovery after a door is left open takes longer.
Long runtime is not automatically a fault. A system running steadily near design conditions dehumidifies well and cycles less. The problem is a unit that cannot catch up on the hottest afternoon of the year.
If it is too large — cooling
It reaches the setpoint quickly and shuts off, then restarts: short cycling.
Because it runs for shorter periods it removes less moisture, so in a humid climate a room can end up cold and still feel clammy. In a dry climate this matters much less.
It costs more to buy, and the extra capacity is doing nothing for most of the season.
If it is too large — heating
Cycling and uneven temperatures, particularly in a room with a single thermostat serving several spaces.
Capacity you paid for and cannot use.
None of this is absolute. A modest oversize is normal practice and often sensible; a variable-capacity or inverter system handles oversizing far better than a single-stage one because it can run at part load rather than only on or off. What matters is knowing roughly where your room sits, which is what the estimate above is for.
Frequently asked questions
How many BTUs do I need per square foot?
There is no single figure. A widely used rule of thumb is about 20 BTU/hr per square foot for cooling, and that is the base this page starts from — but once ceiling height, climate, insulation, sun and occupancy are applied, ordinary rooms in this model land anywhere between about 12 and 47 BTU/hr per square foot. The BTU per square foot table on this page shows the spread by moving one variable at a time.
How many square feet will 12,000 BTU cool?
Under average conditions with an 8 ft ceiling and two people, about 600 square feet on this model. In a shaded, well-insulated room it stretches to roughly 740 square feet; in a hot, poorly insulated, sunny room with four people it drops to about 340. The reverse lookup on this page runs all three and shows the range rather than a single number.
How many square feet will 18,000 BTU cool?
About 900 square feet under average conditions with an 8 ft ceiling and two people, and roughly 510 to 1,110 square feet across the easy and demanding cases the reverse lookup runs. ENERGY STAR’s own chart puts an 18,000 BTU/hr room unit against 700 to 1,000 square feet, which is inside that range.
How many BTUs do I need for 500 square feet?
At the neutral settings this model gives 10,000 BTU/hr for 500 square feet, which points at a 10,000 BTU/hr class. ENERGY STAR’s chart puts 500 square feet in its 450-to-550 band at 12,000 BTU/hr. Which is right depends on the room: a sunny 500 square foot room with a 10 ft ceiling and four people comes out far above both.
How many BTUs do I need for 1,000 square feet?
At the neutral settings this model gives 20,000 BTU/hr, and ENERGY STAR’s chart puts 1,000 square feet at 21,000 BTU/hr — the two are close at this size. A space that large is usually better served by a system sized properly for the whole area than by a single room unit.
Is 12,000 BTU equal to 1 ton?
Yes. For equipment capacity, one ton of refrigeration is defined as exactly 12,000 BTU per hour. It is a definition rather than a measurement, and it has nothing to do with how much the equipment weighs.
How many BTUs are in 1 ton of AC?
Exactly 12,000 BTU per hour. So 1.5 tons is 18,000 BTU/hr, 2 tons is 24,000 BTU/hr, 3 tons is 36,000 BTU/hr, and to go the other way you divide the BTU/hr figure by 12,000.
How do I calculate BTU for a room?
The short version is floor area multiplied by a BTU-per-square-foot rate. The useful version scales that by the actual ceiling height, then adjusts for climate, insulation, sun exposure, what the room is used for and how many people are in it — and, if you can describe the building, replaces the whole thing with a transmission calculation over the walls, windows, roof and floor plus an air-leakage term. Both are on this page, and the second usually differs from the first.
Does ceiling height affect BTU requirements?
Yes, in direct proportion to the extra air. A 10 ft ceiling holds 25% more air than the 8 ft ceiling every square-foot rule of thumb assumes, and this page scales the base load by exactly that. ENERGY STAR states the same basis for its own chart: "The capacities are calculated based on an 8-foot ceiling."
Does insulation affect AC size?
Yes, in both directions. In the quick model, moving from poor to excellent insulation changes the cooling estimate by about 29%. In the advanced model it changes the wall, roof and floor U-factors directly, which is usually a larger effect on heating than on cooling. Insulation is the one input on this page that lowers both your cooling and your heating requirement.
Do windows increase the BTUs I need?
Sunlight through glass is often the single largest cooling load in a room, ahead of everything else combined. West-facing glass is the worst case because the late-afternoon sun strikes it almost head-on at the hottest hour of the day. In the advanced model, window area, glazing type and orientation are separate inputs, and the load breakdown shows what the glass is contributing.
What happens if my AC has too many BTUs?
An oversized unit reaches the thermostat setpoint quickly and shuts off, then restarts — short cycling. Because it runs for shorter periods it removes less moisture, so in a humid climate the room can be cold and still feel clammy. It also costs more to buy. It is not a safety problem, and it does not always cause trouble; in a dry climate the main penalty is the purchase price.
What happens if my AC is undersized?
It runs for longer to reach setpoint, and during a genuine heat peak it may not reach setpoint at all. Long runtimes are not automatically bad — a system that runs steadily near design conditions dehumidifies well — but a unit that cannot catch up on the hottest afternoon of the year was sized for the wrong day.
Are heating BTUs and cooling BTUs calculated the same way?
No, and treating them as the same is a common mistake. Cooling is driven by solar gain through glass, body heat, equipment and a fairly small air-temperature difference. Heating is driven by a large temperature difference, and a heating calculation takes no credit for people, appliances or sunlight, because the system has to hold setpoint on a dark still night when the room is empty.
What is the difference between BTU and BTU/hr?
A BTU is an amount of energy: roughly the energy needed to raise the temperature of one pound of water by one degree Fahrenheit. A BTU per hour is a rate at which energy moves — a power. Equipment capacity is always a rate, so a "12,000 BTU air conditioner" means 12,000 BTU per hour. This page reports rates throughout and labels them that way.
How this calculator works
The quick estimate
Floor area × 20 BTU/hr per ft², scaled by conditioned volume against an 8 ft ceiling, then multiplied by named factors for climate, insulation, sun exposure and room use, then ENERGY STAR’s two published flat allowances — 600 BTU/hr for each occupant above 2, and 4,000 BTU/hr for a kitchen. Heating in quick mode is a ΔT model instead: floor area × a heat-loss rate set by the insulation grade × the temperature difference, scaled by ceiling height. It is deliberately heuristic and the page says so.
The advanced estimate
A transmission and air-change model. Every exterior surface contributes U × A × ΔT: walls net of their glazing, the glazing itself, the ceiling or roof, and the floor at the fraction of ΔT that surface actually sees. Air leakage contributes 0.018 × air changes per hour × room volume × ΔT, a factor derived from an air density of 0.075 lb/ft³ and a specific heat of 0.24 BTU/lb·°F rather than typed in as a constant. Cooling adds solar gain through the glass, occupant sensible and latent heat, and equipment watts. Heating adds none of those.
Why the two estimates differ
They are two models, not two opinions about one calculation, so they will not return the same number. The quick estimate is a generalized room-factor model and is deliberately conservative; the advanced estimate works from the walls, glazing, roof, floor and air-change rate you actually describe, and normally comes out lower for an ordinary room because it stops assuming the worst about the parts of the building it now knows. The result panel always shows what the other tier gives for the same room, so switching between them is never a mystery. Anything you have already typed is kept when you open or close the advanced section — the two tiers share one form.
Units and rounding
The model runs in imperial thermal units because that is what capacity is quoted in worldwide. A metric input is converted exactly once at the boundary through a single conversion library, and the same physical room entered in metres and in feet returns the same load — that is a test in the suite, not an aspiration. Absolute temperatures and temperature differences are separate operations, so the 32-degree offset can never be applied to a ΔT. No intermediate value is ever rounded; rounding happens only for display, and a displayed load is rounded to a readable step because this model does not know a room to the last BTU.
Estimated load versus equipment size
The estimated load is what the model computes. The recommended nominal size is the smallest standard capacity class at or above it. The converted capacity in tons and kilowatts is a unit change of one of those two, and the page always says which. Those three are never merged, and the load is never rounded to a class and then re-presented as the calculation. A recommendation names the nearest appropriate common capacity — it is not a claim that a unit of exactly that size is sold where you live.
Every coefficient, and where it comes from
Every number this page can apply to your room is listed below, with where it comes from. 6 of the 53 are transcribed from a published ENERGY STAR document, 1 is derived from physical limits stated here, and the other 46 are CalcDomain’s own declared model parameters. None of that last group is attributed to anybody, because none of them comes from anybody.
The complete coefficient set, engine v1.0.0 over coefficients v1.0.0.
Coefficient
Value
Basis
What it means
Base factors
Base cooling factor
20 BTU/hr per ft²
CalcDomain model
The starting cooling load per square foot for an ordinary room at an 8 ft ceiling in a moderate climate with average insulation and average sun, before any adjustment.
Sensible heat per occupant
250 BTU/hr per person
CalcDomain model
Dry heat given off by one seated or lightly active adult, the part that raises air temperature.
Latent heat per occupant
200 BTU/hr per person
CalcDomain model
Moisture given off by one seated or lightly active adult, the part a cooling system removes as humidity rather than as temperature.
Additional occupant allowance
600 BTU/hr per person above two
Published
ENERGY STAR: "If more than two people regularly occupy the room, add 600 BTUs for each additional person."
Kitchen allowance
4000 BTU/hr
Published
ENERGY STAR: "If the unit is used in a kitchen, increase capacity by 4,000 BTUs."
Blower-door conversion divisor
÷ 20
CalcDomain model
Divides a 50-pascal blower-door ACH50 to approximate a natural air change rate. A rule of thumb, not a measurement.
Roof assembly U-factor ceiling
0.5 BTU/hr·ft²·°F (R2.0)
Derived
The largest U-factor any opaque roof assembly can physically have, taken as a bare deck with its surface films at about R-2. Caps the product of the insulation grade and the roof condition so the two controls, which describe the same surface, cannot compound into an impossible assembly.
Climate
Cool
×0.85 cooling; design 82°F summer / 5°F winter
CalcDomain model
Short, mild summers and long cold winters — the northern tier.
Moderate
×1.00 cooling; design 90°F summer / 20°F winter
CalcDomain model
Warm summers and cold winters, with neither dominating the year.
Warm
×1.12 cooling; design 95°F summer / 30°F winter
CalcDomain model
Long hot summers and mild winters.
Hot
×1.25 cooling; design 100°F summer / 38°F winter
CalcDomain model
Sustained high summer temperatures; cooling dominates the year.
Very hot
×1.38 cooling; design 105°F summer / 45°F winter
CalcDomain model
Desert or deep-south conditions with extended peaks above 100°F.
Winter severity
Mild
design 35°F outdoors
CalcDomain model
Winter lows around freezing; hard freezes are unusual.
Moderate
design 20°F outdoors
CalcDomain model
Regular sub-freezing nights through the winter.
Cold
design 5°F outdoors
CalcDomain model
Extended periods near and below 0°F.
Very cold
design -10°F outdoors
CalcDomain model
Deep continental winters with sustained sub-zero spells.
High-performance envelope: deep attic insulation at R49–R60 and a well-insulated wall assembly.
Sun exposure
Mostly shaded
×0.90 quick; ×0.35 on window solar gain
Published
ENERGY STAR: "If the room is heavily shaded, reduce capacity by 10 percent."
Average
×1.00 quick; ×0.65 on window solar gain
Published
Neither heavily shaded nor unusually exposed — the ENERGY STAR chart’s own baseline.
Sunny
×1.10 quick; ×0.90 on window solar gain
Published
ENERGY STAR: "If the room is very sunny, increase capacity by 10 percent."
Strong afternoon sun
×1.18 quick; ×1.00 on window solar gain
CalcDomain model
Unshaded west or south-west glass taking the full late-afternoon peak. A CalcDomain extension beyond the two ENERGY STAR steps.
Glazing
Single glazing
U 1.04 BTU/hr·ft²·°F; SHGC 0.76
CalcDomain model
One pane of clear glass. The weakest common assembly by a wide margin.
Double glazing
U 0.49 BTU/hr·ft²·°F; SHGC 0.62
CalcDomain model
Two panes with an air gap and no coating.
Low-E / high performance
U 0.28 BTU/hr·ft²·°F; SHGC 0.31
CalcDomain model
Double glazing with a low-emissivity coating and often an inert gas fill, at about the ENERGY STAR Version 7.0 southern-zone U-factor criterion of 0.28.
Triple glazing
U 0.2 BTU/hr·ft²·°F; SHGC 0.45
CalcDomain model
Three panes, typically coated and gas filled — the lowest heat loss of the four.
Not sure
U 0.49 BTU/hr·ft²·°F; SHGC 0.62
CalcDomain model
Treated as plain double glazing, which is the most common assembly in existing housing. The page shows this as an assumption, not a fact about your window.
Orientation
North
45 BTU/hr·ft² at SHGC 1.0
CalcDomain model
Diffuse sky light only for most of the day.
East
155 BTU/hr·ft² at SHGC 1.0
CalcDomain model
Strong morning peak, before the building has warmed up.
South
110 BTU/hr·ft² at SHGC 1.0
CalcDomain model
Steady midday gain; a high summer sun strikes south glass at a shallow angle.
West
165 BTU/hr·ft² at SHGC 1.0
CalcDomain model
Late-afternoon peak coinciding with the hottest outdoor hour — the worst case for cooling.
Mixed / several directions
115 BTU/hr·ft² at SHGC 1.0
CalcDomain model
Glass facing more than one way; an average across the four exposures.
Roof / ceiling
Heated/cooled room above
excluded from the envelope
CalcDomain model
Another conditioned room sits above, so there is no meaningful loss or gain through this ceiling.
Vented attic above
×1.00 on the roof U-factor; +15°F surface temperature in cooling
CalcDomain model
An unconditioned attic above the ceiling insulation, running hotter than outdoor air on a sunny day.
Insulated roof directly above
×1.00 on the roof U-factor; +5°F surface temperature in cooling
CalcDomain model
A cathedral or insulated flat roof with the insulation in the roof plane.
Uninsulated roof above
U 0.50 absolute (R2.0); +20°F surface temperature in cooling
CalcDomain model
A roof with no meaningful insulation in it — a garage conversion, a porch roof, an older extension. This is a statement about the roof itself, so it sets the assembly U-factor at about R-2 rather than scaling the insulation grade you chose for the rest of the room.
Exposed flat roof
×2.00 on the roof U-factor; +25°F surface temperature in cooling
CalcDomain model
A dark flat roof in full sun with the room directly beneath it.
Floor
Heated/cooled room below
excluded from the envelope
CalcDomain model
Another conditioned room sits below, so there is no meaningful loss or gain through this floor.
Unheated space below
×1.00 on the floor U-factor; sees 50% of ΔT
CalcDomain model
A crawlspace, garage or unheated basement, which tracks about half way between indoors and outdoors.
Slab on ground
×0.60 on the floor U-factor; sees 35% of ΔT
CalcDomain model
A concrete slab on the ground. Deep ground temperature swings far less than the air.
Exposed to outside air
×1.00 on the floor U-factor; sees 100% of ΔT
CalcDomain model
A cantilevered floor or a room over an open carport, with outdoor air beneath it.
Air leakage
Tight / new construction
0.35 air changes per hour
CalcDomain model
Sealed, recently built or deeply retrofitted, usually with mechanical ventilation.
Average
0.7 air changes per hour
CalcDomain model
An ordinary well-kept house with reasonable weatherstripping.
Drafty / older construction
1.1 air changes per hour
CalcDomain model
Noticeable draughts at windows and doors; original sashes.
Very drafty
1.6 air changes per hour
CalcDomain model
Visible gaps, loose sashes or an uninsulated older structure.
Room use
Bedroom
×1.00; default equipment 100 W
CalcDomain model
Low equipment load and mostly evening occupancy.
Living room
×1.00; default equipment 300 W
CalcDomain model
Televisions and entertainment equipment, higher peak occupancy.
Office
×1.05; default equipment 400 W
CalcDomain model
Computers, monitors and lighting running through the hottest part of the day.
Kitchen
×1.00 plus the flat 4,000 BTU/hr kitchen allowance; default equipment 0 W
Published
Cooking appliances. Carries ENERGY STAR’s flat 4,000 BTU/hr kitchen allowance as a separate line rather than a multiplier.
Open-plan space
×1.05; default equipment 300 W
CalcDomain model
A large connected space, harder to condition evenly than a closed room of the same area.
Other
×1.00; default equipment 150 W
CalcDomain model
Anything not covered by the named uses.
Assumptions
Cooling and heating are calculated independently. Changing something only cooling responds to never moves the heating result, and the reverse.
Every area-based factor is stated at the eight-foot ceiling ENERGY STAR names as the basis for its own chart; a different ceiling scales the conditioned volume rather than being ignored.
The occupancy allowance and the kitchen allowance are ENERGY STAR’s published figures, applied as flat additions so they can never be compounded by a multiplier.
The heating model takes no credit for body heat, appliances or sunlight, because a heating system has to reach setpoint when none of them is there.
Occupant moisture is included as a latent cooling load. Humidity carried in by air leakage is not modelled, so a humid coastal room will run above the figure shown.
Where you have not described part of the building, the page uses a declared default and lists it in the assumptions on the result rather than hiding it in the total.
A recommendation names the nearest appropriate common capacity class. It is not a claim that a unit of exactly that size is sold in your market.
A displayed load is rounded for reading only. No intermediate value is ever rounded before the next step consumes it.
Limitations
This is a planning estimate for one room or one connected space, not a whole-building load calculation and not a substitute for a professional design where equipment is being selected for a whole house or anything critical.
The base factor, the condition multipliers, the assembly U-factors, the solar factors and the air-change rates are CalcDomain’s own declared model parameters. They are shown in full on the page with their reasoning; none of them is attributed to an outside publisher, because none of them comes from one.
The ENERGY STAR chart and the ENERGY STAR insulation recommendations are reproduced verbatim from their sources, but they are the publisher’s figures for the publisher’s purpose. The chart sizes room air conditioners and carries no climate, insulation, window or air-leakage adjustment beyond its four stated rules.
Latent load from outdoor humidity is not modelled. In a humid climate, dehumidification is a large part of what a cooling system actually does, and this page does not size for it.
Duct losses, ventilation air, zoning, equipment derating at high outdoor temperature, defrost cycles on a heat pump and part-load behaviour are all outside the model.
Climate bands are planning bands, not location data. If you know your local design temperatures, entering them replaces the band entirely, and the page always prints the two temperatures actually used.
A room over 2,500 square feet, or a load past the top of the capacity ladder, is beyond what a room-level tool can usefully answer, and the page says so instead of extrapolating.
The blower-door conversion divisor is a rule of thumb. It varies with building height, shelter and climate, and the page labels it rather than presenting it as physics.
This calculator provides an estimate for planning and comparison. Building construction, local climate, humidity, ventilation, duct losses and equipment characteristics can all materially change the real HVAC load. For equipment selection in critical or whole-building applications, use an appropriately qualified HVAC professional and a full load calculation.
Sources and review
ENERGY STAR, U.S. Environmental Protection Agency — Room Air Conditioners — cooling capacity chart and sizing adjustments. Retrieved August 19, 2026. Transcribed on 2026-08-19 directly from the table markup of the cited page, then re-read against that markup a second time. No numeric value was changed, interpolated or reconciled with any other source during that review. This is a source-transcription check, not an independent engineering review of ENERGY STAR's own methodology.
ENERGY STAR, U.S. Environmental Protection Agency — Recommended Home Insulation R-Values. Retrieved August 19, 2026. Transcribed on 2026-08-19 directly from the table markup of the cited page and re-read against that markup a second time. No numeric value was changed or reconciled with any other source. This is a source-transcription check, not an independent review of the underlying code requirements.
The two published tables on this page — the ENERGY STAR room air conditioner capacity chart with its four sizing adjustments, and the ENERGY STAR recommended insulation R-values with their 2021 IECC basis — were transcribed cell by cell from the publisher pages and re-read against that markup a second time on 2026-08-19. That is a source-transcription check, NOT an independent third-party engineering review: no outside HVAC engineer has reviewed the load model, and this page does not claim one. Correctness of the arithmetic is enforced by the contract archetype’s golden vectors, the twelve permanent engine fixtures, the metric–imperial equivalence suite, the breakdown reconciliation checks that fail closed rather than print a total its own parts do not add up to, the fail-closed dataset validators proved against deliberately broken fixtures, and the dedicated renderer suite. Every coefficient that is CalcDomain’s own is labelled as a model parameter on the page rather than dressed as a published constant.
Written by Ugo Candido. Last reviewed August 19, 2026. Engine v1.0.0, coefficients v1.0.0, units v1.0.0.