BTU Calculator — AC, Heating and Room Size

Calculate how many BTUs you need for an air conditioner, a heater or a room. Adjust for size, ceiling height, climate, insulation, sunlight and occupancy — and see exactly which of them is driving the number.

Cooling and heating are calculated separately — a heating load is not a cooling load reused. Start with the quick estimate; open Improve this estimate when you can describe the building itself.

Your room

How do you want to give the room size?

The longer side of the room.

The shorter side of the room.

Cooling and heating a room is about its volume. 8 ft is the basis ENERGY STAR states for its own chart, and a taller ceiling raises the load in proportion.

Unsure? Use Moderate, or enter your own outdoor design temperature under Improve this estimate. The result always prints the temperature it actually used.

The middle two options are ENERGY STAR’s own ±10% shade and sun rules.

A kitchen carries ENERGY STAR’s flat 4,000 BTU/hr allowance as its own line, so it is never counted twice.

ENERGY STAR adds 600 BTU/hr for each person above two. At two or fewer, nothing is added.

How well the room holds temperature. The same grade sets the wall, roof and floor U-factors the advanced model uses — see the insulation table below for what each grade means against the published code recommendations.

Improve this estimate — describe the building

Everything below is optional. Anything you leave alone keeps a declared default, and the result lists every default it used. Filling these in switches the page from the room-size model to a transmission model over the actual envelope.

Temperatures and exterior walls

Leave blank to use 75°F for cooling and 70°F for heating.

The temperature you are sizing against — not the annual record. Leave blank to use the climate band you chose above.

How many of this room’s walls face outdoors. Leave on the blank option to assume a corner room with two.

Windows
How do you want to give the window area?

All the glass in this room added together. Leave blank to assume 15% of the exterior wall.

Not sure? It is treated as plain double glazing, and the result says so. Single glazing loses more than three times as much heat as low-E.

From the sticker on the window. Overrides the glazing choice entirely.

Solar heat gain coefficient, 0 to 1, from the same sticker.

West is the worst case: the late-afternoon sun strikes west glass almost head-on at the hottest hour of the day.

Above and below

A vented attic in the sun runs well above outdoor air temperature, which is why a top-floor room is harder to cool than the floor below it.

A crawlspace sits about half way between indoors and outdoors; ground under a slab barely moves.

Air leakage and internal heat

Air changes per hour under ordinary conditions — not the 50-pascal figure a blower-door test reports.

An ACH50 is divided by 20 to approximate a natural rate. That divisor is a rule of thumb, and the result says so.

Add up what runs during the hottest part of the day. A desktop and two monitors is roughly 250 W; a large TV about 120 W; a fridge about 150 W averaged.

Your result

Recommended cooling capacity12,000BTU/hr1.00 tons · 3.52 kW

Estimated cooling load: 10,500 BTU/hr — that is the calculation. 12,000 BTU/hr is the nearest appropriate common capacity class at or above it, which is a different number and is chosen, not computed.

Estimate quality: Basic This is the quick estimate: a room-size model with named adjustments. Open Improve this estimate to describe the building itself.

The advanced estimate gives 8,300 BTU/hr for this room — 21% lower than the figure above. The advanced estimate works from the actual walls, glazing, roof, floor and air-change rate instead of generalized room factors, and is normally the more tailored of the two. It is showing a default building description until you fill some of it in.

Where your BTUs come from

Load componentBTU/hrShareRelative size
Room and envelope8,00077%
Climate9609%
Windows and sun8969%
Equipment00%
Occupants6006%
Estimated cooling load10,456100%

Largest driver: room and envelope, at 77% of the total.

What is driving this result

  • Sunny is one of the reasons this estimate is above what floor area alone would suggest. Shading that glass is usually cheaper than buying capacity to fight it.
Cross-check against the ENERGY STAR chart

The ENERGY STAR figure is a recommended equipment capacity, not a calculated thermal load. It is compared here against this page’s recommended nominal size, which is the same kind of quantity. The estimated load is shown separately and is expected to sit below both.

For a 400 up to 450 ft² room.
FigureBTU/hrWhat it is
ENERGY STAR capacity10,000A recommended room air conditioner size
This page, nominal size12,000The same kind of quantity, 20% higher
This page, estimated load10,456A calculated thermal load. Expected to sit below both — it carries no sizing margin

The two are different instruments and are not expected to land on the same figure. The published chart is a room-unit selection table calculated on an 8 ft ceiling, and it carries no adjustment beyond shade, sun, extra occupants and a kitchen. Here, the difference comes from:

  • the chart carries no climate adjustment and this room is in a warm climate
  • sun exposure is set to sunny
  • there are 3 occupants rather than the chart’s baseline of 2
  • the chart is banded, so one capacity covers every room from 400 to 450 ft² — a 13% spread in floor area answered by a single figure
  • a published capacity is rounded up to a unit you can actually buy, so it carries a sizing margin a calculated load does not
See how this result was calculated
  1. Base room load+8,000 BTU/hr400 ft² × 20 BTU/hr per ft² at an 8 ft ceilingrunning total 8,000 BTU/hr
  2. Ceiling height+0 BTU/hr8.0 ft ceiling is 0% more air than the 8 ft basisrunning total 8,000 BTU/hr
  3. Climate+960 BTU/hrWarm climate, ×1.12running total 8,960 BTU/hr
  4. Insulation+0 BTU/hrAverage insulation, ×1.00running total 8,960 BTU/hr
  5. Sun exposure+896 BTU/hrSunny, ×1.10running total 9,856 BTU/hr
  6. Room use+0 BTU/hrLiving room, ×1.00running total 9,856 BTU/hr
  7. Occupants+600 BTU/hr3 people; ENERGY STAR adds 600 BTU/hr for each person above 2running total 10,456 BTU/hr

Estimated load 10,456 BTU/hr, displayed as 10,500 BTU/hr because this model does not know a room to the last BTU. The recommendation step then selects the smallest capacity class at or above it: 12,000 BTU/hr, leaving 1,544 BTU/hr of headroom.

Conditions actually used

Indoor target
75°F
Outdoor design
95°F
Floor area
400 ft²
Ceiling height
8.0 ft
Conditioned volume
3,200 ft³
Engine
btu-calculator v1.0.0 · coefficients v1.0.0

Assumptions this result rests on

  • Exterior walls not entered — assumed 2, a corner room.
  • Window area not entered — assumed 15% of the exterior wall area, about 48 ft².
  • Glazing not identified — treated as plain double glazing (U 0.49, SHGC 0.62).
  • Equipment heat not entered — the living room default of 300 W is used.
  • What is above the ceiling was left on the default — treated as a vented attic above.
  • What is below the floor was left on the default — treated as an unheated space below.
  • Indoor target 75°F, outdoor design temperature 95°F.
  • Quick estimate: a room-size model with named adjustments, including ENERGY STAR’s own occupancy and kitchen rules.

See what changes your BTU requirement

Each row below is this same room recalculated with one thing changed, through the identical engine — not a rule of thumb about what improvements usually do.

ChangeEstimated loadDifferenceNominal size
As entered now10,500 BTU/hr12,000 BTU/hr
Improve insulation to good9,450 BTU/hr−986 (−9.4%)10,000 BTU/hr changes the class
Shade the windows8,650 BTU/hr−1,792 (−17.1%)9,000 BTU/hr changes the class

Glazing and air-sealing scenarios appear once you open Improve this estimate: the quick model has no window U-factor and no air-change term for them to act on.

How many BTUs do I need?

Enough to remove the heat that actually enters the room, or to replace the heat that actually leaves it. That is a different quantity for every room, which is why the honest answer starts with a question rather than a number.

For a rough anchor: an ordinary 400 square foot room with a standard 8 ft ceiling, in a moderate climate with average insulation and average sun and two people in it, comes out at 8,000 BTU/hr of cooling on this model, pointing at a 8,000 BTU/hr class. Move that same room somewhere hot, raise the ceiling, take the shade away and add three more people and it is nearly double.

Three things decide how far the answer moves: how much air there is (floor area times ceiling height, not floor area alone), how easily heat crosses the envelope (insulation, glazing, what is above and below, how draughty it is) and how much heat is already inside or arriving through the glass (sunlight, people, equipment). The calculator above walks through all three; the load breakdown shows which one is dominating your room.

BTU per square foot

“BTU per square foot” is a rule of thumb, not a constant. About 20 BTU/hr per square foot is the figure the category is built on, and it is where this model starts — but square footage alone cannot account for ceiling height, insulation, windows, sun exposure, occupancy or outdoor temperature, and every one of those moves the rate.

The same 400 ft² room, with one thing changed at a time. Generated by the calculator on this page, not typed in separately.
ConditionBTU/hr per ft²Estimated loadNominal size
Baseline: moderate climate, average insulation, average sun, 8 ft ceiling 20.0 8,000 8,000
Cool climate 17.0 6,800 8,000
Moderate climate 20.0 8,000 8,000
Warm climate 22.4 8,960 9,000
Hot climate 25.0 10,000 10,000
Very hot climate 27.6 11,040 12,000
Poor insulation 23.0 9,200 10,000
Average insulation 20.0 8,000 8,000
Good insulation 18.0 7,200 8,000
Excellent insulation 16.4 6,560 8,000
Mostly shaded 18.0 7,200 8,000
Average 20.0 8,000 8,000
Sunny 22.0 8,800 9,000
Strong afternoon sun 23.6 9,440 10,000
10 ft ceiling 25.0 10,000 10,000
Five occupants 24.5 9,800 10,000

Across those cases alone the implied rate runs from 16.4 to 27.6 BTU/hr per square foot — a 1.7-fold spread on one unchanged floor area.

Even the published ENERGY STAR chart does not imply a constant. Read across its own rows, the capacity per square foot at the bottom of each band falls from about 50 BTU/hr per ft² at the small end to about 17 at the large end. A small room carries a fixed overhead that a large one spreads out.

The published chart, in full

ENERGY STAR’s published room air conditioner cooling capacity chart, reproduced in full. The third column is arithmetic on the publisher’s own figures, not a published value.
Area to be cooled (sq ft)Capacity needed (BTU/hr)Implied BTU/hr per ft² at the low end
100 up to 150 5,000 50.0
150 up to 250 6,000 40.0
250 up to 300 7,000 28.0
300 up to 350 8,000 26.7
350 up to 400 9,000 25.7
400 up to 450 10,000 25.0
450 up to 550 12,000 26.7
550 up to 700 14,000 25.5
700 up to 1,000 18,000 25.7
1,000 up to 1,200 21,000 21.0
1,200 up to 1,400 23,000 19.2
1,400 up to 1,500 24,000 17.1
1,500 up to 2,000 30,000 20.0
2,000 up to 2,500 34,000 17.0

The capacities are calculated based on an 8-foot ceiling. If you have higher ceilings, you may want to select a room air conditioner with a higher CADR.

The publisher then lists four adjustments, quoted here exactly as written:

Source: ENERGY STAR, U.S. Environmental Protection Agency — Room Air Conditioners — cooling capacity chart and sizing adjustments. Retrieved August 19, 2026. This chart sizes ROOM air conditioners for a single room. It is not a whole-house load calculation, it carries no climate, insulation, window or air-leakage adjustment beyond the four listed above, and the publisher states no BTU-per-square-foot constant anywhere — the implied rate varies from about 33 BTU/hr per ft² at the small end of the chart to about 17 at the large end.

BTU calculator by room size

Starting estimates for common room sizes, generated by the calculator above at a fixed set of assumptions and shown next to what the published ENERGY STAR chart gives for the same area. The ENERGY STAR figure is a recommended equipment capacity, so the column to read it against is Common AC size. Setting it beside the estimated load instead would put a product size next to a thermal load and read the chart’s built-in sizing margin as a disagreement. Where the two capacities still differ, the reason is one of the things the chart does not ask about, or the width of the band it answers.

Starting estimates by room area. Assumptions: an 8 ft ceiling, a moderate climate, average insulation, average sun exposure, two occupants and ordinary room use. Change any one of those and the figure moves — that is the point of the calculator above. Read the last column against Common AC size, not against the estimated load: both of those are capacities, and the load is not.
Room area Estimated load Common AC size BTU/hr per ft² ENERGY STAR capacity
100 sq ft 2,000 BTU/hr 5,000 BTU/hr 20.0 5,000 BTU/hr
150 sq ft 3,000 BTU/hr 5,000 BTU/hr 20.0 6,000 BTU/hr
200 sq ft 4,000 BTU/hr 5,000 BTU/hr 20.0 6,000 BTU/hr
250 sq ft 5,000 BTU/hr 5,000 BTU/hr 20.0 7,000 BTU/hr
300 sq ft 6,000 BTU/hr 6,000 BTU/hr 20.0 8,000 BTU/hr
400 sq ft 8,000 BTU/hr 8,000 BTU/hr 20.0 10,000 BTU/hr
500 sq ft 10,000 BTU/hr 10,000 BTU/hr 20.0 12,000 BTU/hr
600 sq ft 12,000 BTU/hr 12,000 BTU/hr 20.0 14,000 BTU/hr
750 sq ft 15,000 BTU/hr 15,000 BTU/hr 20.0 18,000 BTU/hr
1,000 sq ft 20,000 BTU/hr 20,000 BTU/hr 20.0 21,000 BTU/hr
1,200 sq ft 24,000 BTU/hr 24,000 BTU/hr 20.0 23,000 BTU/hr
1,500 sq ft 30,000 BTU/hr 30,000 BTU/hr 20.0 30,000 BTU/hr

Use these to sanity-check a quote or narrow a shortlist. Do not use them instead of the calculator: every row assumes a standard ceiling, average insulation, moderate exposure, two occupants and a moderate climate, and changing any one of those is worth more than moving up a row.

How to calculate BTU for an air conditioner

The short version, and the one every “BTU calculator” on the web implements:

BTU/hr ≈ floor area (ft²) × BTU per ft²

It is a shortcut, and it is worth knowing exactly what it leaves out. It assumes an 8 ft ceiling, an average climate, an average envelope, average glass and two people. Four of those five are usually wrong for the room you are actually standing in.

A more useful calculation considers

That is what Improve this estimate switches the calculator over to. Instead of one multiplier chain it computes each path heat takes into the room and adds them up:

Q_cooling = Σ(U × A × ΔT) + solar through glass + occupants + equipment + air leakage

where the solar term is window area × an orientation-dependent peak irradiance × the glazing SHGC × a shading factor, and the air leakage term is 0.075 lb/ft³ × 0.24 BTU/lb·°F × air changes per hour × room volume × ΔT.

How to calculate heating BTUs

Heating is a cleaner calculation than cooling, because there is no sun and no useful internal gain to argue about. Everything comes down to a temperature difference across a surface:

Q_heating = Σ(U × A × ΔT) + air leakage, where ΔT = indoor target − outdoor design temperature

The ΔT is the whole story, and it is exactly what a per-square-foot heating rule of thumb hides. Holding 70°F against a 35°F night is a 35°F difference; holding the same temperature against -10°F is 80°F — more than twice the load for exactly the same room.

Two rules this page follows that simple heating calculators usually do not:

Note also that a furnace is often rated by input rather than output. A 80,000 BTU/hr furnace at 80% efficiency delivers about 64,000 BTU/hr into the house. This page estimates the heat the room needs — the output — so compare it against an output rating, not an input one.

What affects the BTU requirement?

In rough order of how much they usually move the number for a single room:

  1. Sunlight through glass. In the advanced model this is frequently the largest single line. West-facing glass is the worst case at 165 BTU/hr per square foot of glass at peak, against 45 for north-facing.
  2. The temperature difference. Every transmission term is directly proportional to it, so the design temperature you size against matters as much as the building does.
  3. Insulation. Between the poorest and best grades this model uses, the wall U-factor changes by a factor of 6.3 and the roof by 15.0.
  4. Ceiling height. It scales the conditioned volume directly, and it is the input people most often forget to change.
  5. What is above the ceiling. A sunlit attic runs about 15°F above outdoor air; an uninsulated roof in full sun, about 25°F above. That is why top-floor rooms are the hard ones.
  6. Air leakage. Between a tight room and a very draughty one this model moves the air-change rate from 0.35 to 1.60 per hour — a factor of 4.6 on that whole term.
  7. People and equipment. Each occupant adds about 450 BTU/hr of cooling load, and every watt of equipment running becomes 3.41 BTU/hr of heat.

What “good insulation” actually means

“Good insulation” is not a measurement, so it is worth anchoring it to something that is. ENERGY STAR publishes recommended R-values by United States climate zone, based on the 2021 IECC:

ENERGY STAR recommended home insulation R-values — what a well-insulated assembly should reach, by United States climate zone. The first attic column applies where the attic is uninsulated; the second applies where three to four inches of insulation are already present.
Climate zoneAttic, if uninsulatedAttic, if 3–4 in alreadyFloor
Zone 1 R30 R25 R13
Zone 2 R49 R38 R13
Zone 3 R49 R38 R19
Zone 4A and 4B R60 R49 R19
Zone 6, 5, and 4C R60 R49 R30
Zone 7 and 8 R60 R49 R38

This guidance is based on the 2021 International Energy Conservation Code (IECC) Residential Provisions Chapter 4 Table R402.1.3. See Code for more detailed guidance. Source: ENERGY STAR, U.S. Environmental Protection Agency — Recommended Home Insulation R-Values. Retrieved August 19, 2026. These are recommended R-values for insulation work, not measured assembly U-factors for an existing building, and they are retrofit guidance for wood-framed housing in United States climate zones. They tell you what a well-insulated assembly should reach; they do not tell you what your wall is today.

Those are the figures to aim for. What the calculator needs is what your room is today, so the four grades it offers translate as follows — and these R-values are CalcDomain’s own model parameters, not the publisher’s:

What each insulation grade means inside this model.
GradeDescribesWallRoofFloor
Poor Little or no cavity insulation — an uninsulated wood-frame assembly or an older solid wall. R4 R3 R4
Average Insulated cavities but no continuous exterior insulation — a typical existing home. R10 R20 R13
Good A code-compliant retrofit: full cavity insulation plus continuous sheathing, attic at about R30. R17 R30 R20
Excellent High-performance envelope: deep attic insulation at R49–R60 and a well-insulated wall assembly. R25 R50 R30

What room size can my AC cool?

The same model, run backwards. Enter a capacity and it solves for the area whose estimated load equals it — under three different sets of room conditions, because a single square-footage answer would be the same mistake this page exists to avoid.

Try 5,000 · 8,000 · 12,000 · 18,000 · 24,000 — or the number on your own unit.

A 12,000 BTU/hr unit covers roughly 342–741 ft², depending entirely on the room.

Room conditionsArea it coversImplied BTU/hr per ft²
Shaded, well insulated, two people741 ft²16.2
Average room, average sun, two people600 ft²20.0
Sunny, poorly insulated, four people342 ft²31.6

Sunny rooms, high ceilings, poor insulation and more occupants all reduce the area one unit can comfortably serve. These figures invert this page’s own quick cooling model at an 8 ft ceiling; they are not a manufacturer’s coverage claim.

A 12,000 BTU/hr unit covers roughly 342–741 sq ft depending on the room, and an 18,000 BTU/hr unit roughly 531–1,111 sq ft. Here is the whole ladder:

How much room each common capacity can serve, at an 8 ft ceiling. The typical column is an average room; the range spans a shaded well-insulated room with two people at one end and a hot, poorly insulated, sunny room with four at the other.
Unit capacityTonsTypical roomRange across conditions
5,000 BTU/hr 0.42 250 sq ft 120–309 sq ft
6,000 BTU/hr 0.50 300 sq ft 152–370 sq ft
8,000 BTU/hr 0.67 400 sq ft 215–494 sq ft
10,000 BTU/hr 0.83 500 sq ft 278–617 sq ft
12,000 BTU/hr 1.00 600 sq ft 342–741 sq ft
14,000 BTU/hr 1.17 700 sq ft 405–864 sq ft
18,000 BTU/hr 1.50 900 sq ft 531–1,111 sq ft
24,000 BTU/hr 2.00 1,200 sq ft 721–1,481 sq ft
36,000 BTU/hr 3.00 1,800 sq ft 1,100–2,222 sq ft

BTU to tons

For equipment capacity, one ton of refrigeration is defined as exactly 12,000 BTU per hour. It is a definition rather than a measurement, and it says nothing about how much the equipment weighs — the name is a historical hangover from the rate of cooling produced by a ton of melting ice in a day.

tons = BTU/hr ÷ 12,000 · BTU/hr = tons × 12,000

BTU/hr ⇄ tons

Type in either box. 18,000 BTU/hr is 1.50 tons.

The common sizes

TonsBTU/hr
0.506,000
0.759,000
1.0012,000
1.5018,000
2.0024,000
2.5030,000
3.0036,000
4.0048,000
5.0060,000

BTU to watts and kW

A BTU per hour and a watt are both units of power, so converting between them is exact. Using the International Table BTU of 1055.05585262 joules:

1 BTU/hr = 0.293071 W · 1 kW = 3,412.142 BTU/hr

BTU/hr ⇄ W ⇄ kW

Type in any box and the other two follow.

This is a capacity conversion, not an electricity bill

A 12,000 BTU/hr air conditioner does not draw 3.52 kW from the wall. That figure is the rate at which it moves heat out of the room, not the electrical power it consumes to do it. A heat pump or air conditioner moves several units of heat for each unit of electricity, so actual consumption is a fraction of the capacity — how big a fraction is what SEER, EER and COP ratings describe. Converting capacity to watts tells you nothing about running cost on its own.

What is a BTU?

A British thermal unit is an amount of energy: approximately the energy needed to raise the temperature of one pound of water by one degree Fahrenheit, under defined conditions. Precisely, the International Table BTU used for equipment ratings is defined as 1055.05585262 joules.

A BTU per hour is something different — a rate at which energy moves, which is to say a power, in the same family as the watt. That distinction is the one thing worth taking away from this page:

Everything this calculator produces is a rate, in BTU per hour, and every label on the page says so.

BTU calculation examples

Three rooms, run through the calculator above at build time. Every figure here is produced by the same engine, so if a coefficient changes these change with it.

Example 1 — sizing an air conditioner for a bedroom

A 12 × 12 ft bedroom with a standard ceiling, in a moderate climate, average insulation, average sun, two people.

Estimated cooling load: 2,900 BTU/hr
Nearest common capacity class: 5,000 BTU/hr — 0.42 tons, 1.47 kW

Where that load comes from. Computed live by the same engine the calculator runs, so these figures cannot drift from the tool above.
ComponentBTU/hrShare
Room and envelope2,880100%
Climate00%
Windows and sun00%
Equipment00%
Occupants00%

Example 2 — the same floor area, a sunny living room

A 400 ft² living room with a 10 ft ceiling in a hot climate, poorly insulated, taking the full afternoon sun, with five people in it.

Estimated cooling load: 18,800 BTU/hr
Nearest common capacity class: 20,000 BTU/hr — 1.67 tons, 5.86 kW

Where that load comes from. Computed live by the same engine the calculator runs, so these figures cannot drift from the tool above.
ComponentBTU/hrShare
Room and envelope11,87563%
Climate2,50013%
Windows and sun2,58814%
Equipment00%
Occupants1,80010%

Example 3 — heating a room in a cold climate

The same 400 ft² room, this time being heated to 70°F against a 5°F outdoor design temperature, with the full envelope described.

Estimated heating load: 8,550 BTU/hr
Nearest common capacity class: 10,000 BTU/hr — 0.83 tons, 2.93 kW

Where that load comes from. Computed live by the same engine the calculator runs, so these figures cannot drift from the tool above.
ComponentBTU/hrShare
Room and envelope4,03047%
Windows and sun1,91122%
Air leakage2,62131%

Two 400 sq ft rooms can need very different capacities

Room A

10 ft ceiling · poor insulation · unshaded west-facing afternoon sun · five people

18,800 BTU/hr

Nearest class 20,000 BTU/hr · 1.67 tons · 46.9 BTU/hr per ft²

Room B

8 ft ceiling · excellent insulation · shaded · two people

5,000 BTU/hr

Nearest class 6,000 BTU/hr · 0.50 tons · 12.5 BTU/hr per ft²

Both rooms are 400 square feet. Room A needs about 3.7× the cooling capacity of Room B — 13,744 BTU/hr more — and lands 8 capacity classes higher. Any calculator that answers “how many BTUs for 400 square feet?” with a single number is answering a question nobody actually has.

Why the right BTU size matters

If it is too small

If it is too large — cooling

If it is too large — heating

None of this is absolute. A modest oversize is normal practice and often sensible; a variable-capacity or inverter system handles oversizing far better than a single-stage one because it can run at part load rather than only on or off. What matters is knowing roughly where your room sits, which is what the estimate above is for.

Frequently asked questions

How many BTUs do I need per square foot?

There is no single figure. A widely used rule of thumb is about 20 BTU/hr per square foot for cooling, and that is the base this page starts from — but once ceiling height, climate, insulation, sun and occupancy are applied, ordinary rooms in this model land anywhere between about 12 and 47 BTU/hr per square foot. The BTU per square foot table on this page shows the spread by moving one variable at a time.

How many square feet will 12,000 BTU cool?

Under average conditions with an 8 ft ceiling and two people, about 600 square feet on this model. In a shaded, well-insulated room it stretches to roughly 740 square feet; in a hot, poorly insulated, sunny room with four people it drops to about 340. The reverse lookup on this page runs all three and shows the range rather than a single number.

How many square feet will 18,000 BTU cool?

About 900 square feet under average conditions with an 8 ft ceiling and two people, and roughly 510 to 1,110 square feet across the easy and demanding cases the reverse lookup runs. ENERGY STAR’s own chart puts an 18,000 BTU/hr room unit against 700 to 1,000 square feet, which is inside that range.

How many BTUs do I need for 500 square feet?

At the neutral settings this model gives 10,000 BTU/hr for 500 square feet, which points at a 10,000 BTU/hr class. ENERGY STAR’s chart puts 500 square feet in its 450-to-550 band at 12,000 BTU/hr. Which is right depends on the room: a sunny 500 square foot room with a 10 ft ceiling and four people comes out far above both.

How many BTUs do I need for 1,000 square feet?

At the neutral settings this model gives 20,000 BTU/hr, and ENERGY STAR’s chart puts 1,000 square feet at 21,000 BTU/hr — the two are close at this size. A space that large is usually better served by a system sized properly for the whole area than by a single room unit.

Is 12,000 BTU equal to 1 ton?

Yes. For equipment capacity, one ton of refrigeration is defined as exactly 12,000 BTU per hour. It is a definition rather than a measurement, and it has nothing to do with how much the equipment weighs.

How many BTUs are in 1 ton of AC?

Exactly 12,000 BTU per hour. So 1.5 tons is 18,000 BTU/hr, 2 tons is 24,000 BTU/hr, 3 tons is 36,000 BTU/hr, and to go the other way you divide the BTU/hr figure by 12,000.

How do I calculate BTU for a room?

The short version is floor area multiplied by a BTU-per-square-foot rate. The useful version scales that by the actual ceiling height, then adjusts for climate, insulation, sun exposure, what the room is used for and how many people are in it — and, if you can describe the building, replaces the whole thing with a transmission calculation over the walls, windows, roof and floor plus an air-leakage term. Both are on this page, and the second usually differs from the first.

Does ceiling height affect BTU requirements?

Yes, in direct proportion to the extra air. A 10 ft ceiling holds 25% more air than the 8 ft ceiling every square-foot rule of thumb assumes, and this page scales the base load by exactly that. ENERGY STAR states the same basis for its own chart: "The capacities are calculated based on an 8-foot ceiling."

Does insulation affect AC size?

Yes, in both directions. In the quick model, moving from poor to excellent insulation changes the cooling estimate by about 29%. In the advanced model it changes the wall, roof and floor U-factors directly, which is usually a larger effect on heating than on cooling. Insulation is the one input on this page that lowers both your cooling and your heating requirement.

Do windows increase the BTUs I need?

Sunlight through glass is often the single largest cooling load in a room, ahead of everything else combined. West-facing glass is the worst case because the late-afternoon sun strikes it almost head-on at the hottest hour of the day. In the advanced model, window area, glazing type and orientation are separate inputs, and the load breakdown shows what the glass is contributing.

What happens if my AC has too many BTUs?

An oversized unit reaches the thermostat setpoint quickly and shuts off, then restarts — short cycling. Because it runs for shorter periods it removes less moisture, so in a humid climate the room can be cold and still feel clammy. It also costs more to buy. It is not a safety problem, and it does not always cause trouble; in a dry climate the main penalty is the purchase price.

What happens if my AC is undersized?

It runs for longer to reach setpoint, and during a genuine heat peak it may not reach setpoint at all. Long runtimes are not automatically bad — a system that runs steadily near design conditions dehumidifies well — but a unit that cannot catch up on the hottest afternoon of the year was sized for the wrong day.

Are heating BTUs and cooling BTUs calculated the same way?

No, and treating them as the same is a common mistake. Cooling is driven by solar gain through glass, body heat, equipment and a fairly small air-temperature difference. Heating is driven by a large temperature difference, and a heating calculation takes no credit for people, appliances or sunlight, because the system has to hold setpoint on a dark still night when the room is empty.

What is the difference between BTU and BTU/hr?

A BTU is an amount of energy: roughly the energy needed to raise the temperature of one pound of water by one degree Fahrenheit. A BTU per hour is a rate at which energy moves — a power. Equipment capacity is always a rate, so a "12,000 BTU air conditioner" means 12,000 BTU per hour. This page reports rates throughout and labels them that way.

How this calculator works

The quick estimate

Floor area × 20 BTU/hr per ft², scaled by conditioned volume against an 8 ft ceiling, then multiplied by named factors for climate, insulation, sun exposure and room use, then ENERGY STAR’s two published flat allowances — 600 BTU/hr for each occupant above 2, and 4,000 BTU/hr for a kitchen. Heating in quick mode is a ΔT model instead: floor area × a heat-loss rate set by the insulation grade × the temperature difference, scaled by ceiling height. It is deliberately heuristic and the page says so.

The advanced estimate

A transmission and air-change model. Every exterior surface contributes U × A × ΔT: walls net of their glazing, the glazing itself, the ceiling or roof, and the floor at the fraction of ΔT that surface actually sees. Air leakage contributes 0.018 × air changes per hour × room volume × ΔT, a factor derived from an air density of 0.075 lb/ft³ and a specific heat of 0.24 BTU/lb·°F rather than typed in as a constant. Cooling adds solar gain through the glass, occupant sensible and latent heat, and equipment watts. Heating adds none of those.

Why the two estimates differ

They are two models, not two opinions about one calculation, so they will not return the same number. The quick estimate is a generalized room-factor model and is deliberately conservative; the advanced estimate works from the walls, glazing, roof, floor and air-change rate you actually describe, and normally comes out lower for an ordinary room because it stops assuming the worst about the parts of the building it now knows. The result panel always shows what the other tier gives for the same room, so switching between them is never a mystery. Anything you have already typed is kept when you open or close the advanced section — the two tiers share one form.

Units and rounding

The model runs in imperial thermal units because that is what capacity is quoted in worldwide. A metric input is converted exactly once at the boundary through a single conversion library, and the same physical room entered in metres and in feet returns the same load — that is a test in the suite, not an aspiration. Absolute temperatures and temperature differences are separate operations, so the 32-degree offset can never be applied to a ΔT. No intermediate value is ever rounded; rounding happens only for display, and a displayed load is rounded to a readable step because this model does not know a room to the last BTU.

Estimated load versus equipment size

The estimated load is what the model computes. The recommended nominal size is the smallest standard capacity class at or above it. The converted capacity in tons and kilowatts is a unit change of one of those two, and the page always says which. Those three are never merged, and the load is never rounded to a class and then re-presented as the calculation. A recommendation names the nearest appropriate common capacity — it is not a claim that a unit of exactly that size is sold where you live.

Every coefficient, and where it comes from

Every number this page can apply to your room is listed below, with where it comes from. 6 of the 53 are transcribed from a published ENERGY STAR document, 1 is derived from physical limits stated here, and the other 46 are CalcDomain’s own declared model parameters. None of that last group is attributed to anybody, because none of them comes from anybody.

The complete coefficient set, engine v1.0.0 over coefficients v1.0.0.
CoefficientValueBasisWhat it means
Base factors
Base cooling factor 20 BTU/hr per ft² CalcDomain model The starting cooling load per square foot for an ordinary room at an 8 ft ceiling in a moderate climate with average insulation and average sun, before any adjustment.
Sensible heat per occupant 250 BTU/hr per person CalcDomain model Dry heat given off by one seated or lightly active adult, the part that raises air temperature.
Latent heat per occupant 200 BTU/hr per person CalcDomain model Moisture given off by one seated or lightly active adult, the part a cooling system removes as humidity rather than as temperature.
Additional occupant allowance 600 BTU/hr per person above two Published ENERGY STAR: "If more than two people regularly occupy the room, add 600 BTUs for each additional person."
Kitchen allowance 4000 BTU/hr Published ENERGY STAR: "If the unit is used in a kitchen, increase capacity by 4,000 BTUs."
Blower-door conversion divisor ÷ 20 CalcDomain model Divides a 50-pascal blower-door ACH50 to approximate a natural air change rate. A rule of thumb, not a measurement.
Roof assembly U-factor ceiling 0.5 BTU/hr·ft²·°F (R2.0) Derived The largest U-factor any opaque roof assembly can physically have, taken as a bare deck with its surface films at about R-2. Caps the product of the insulation grade and the roof condition so the two controls, which describe the same surface, cannot compound into an impossible assembly.
Climate
Cool ×0.85 cooling; design 82°F summer / 5°F winter CalcDomain model Short, mild summers and long cold winters — the northern tier.
Moderate ×1.00 cooling; design 90°F summer / 20°F winter CalcDomain model Warm summers and cold winters, with neither dominating the year.
Warm ×1.12 cooling; design 95°F summer / 30°F winter CalcDomain model Long hot summers and mild winters.
Hot ×1.25 cooling; design 100°F summer / 38°F winter CalcDomain model Sustained high summer temperatures; cooling dominates the year.
Very hot ×1.38 cooling; design 105°F summer / 45°F winter CalcDomain model Desert or deep-south conditions with extended peaks above 100°F.
Winter severity
Mild design 35°F outdoors CalcDomain model Winter lows around freezing; hard freezes are unusual.
Moderate design 20°F outdoors CalcDomain model Regular sub-freezing nights through the winter.
Cold design 5°F outdoors CalcDomain model Extended periods near and below 0°F.
Very cold design -10°F outdoors CalcDomain model Deep continental winters with sustained sub-zero spells.
Insulation
Poor ×1.15 cooling; 0.55 BTU/hr·ft²·°F quick heating; U wall 0.25 / roof 0.3 / floor 0.25 CalcDomain model Little or no cavity insulation — an uninsulated wood-frame assembly or an older solid wall.
Average ×1.00 cooling; 0.38 BTU/hr·ft²·°F quick heating; U wall 0.1 / roof 0.05 / floor 0.08 CalcDomain model Insulated cavities but no continuous exterior insulation — a typical existing home.
Good ×0.90 cooling; 0.28 BTU/hr·ft²·°F quick heating; U wall 0.06 / roof 0.033 / floor 0.05 CalcDomain model A code-compliant retrofit: full cavity insulation plus continuous sheathing, attic at about R30.
Excellent ×0.82 cooling; 0.2 BTU/hr·ft²·°F quick heating; U wall 0.04 / roof 0.02 / floor 0.033 CalcDomain model High-performance envelope: deep attic insulation at R49–R60 and a well-insulated wall assembly.
Sun exposure
Mostly shaded ×0.90 quick; ×0.35 on window solar gain Published ENERGY STAR: "If the room is heavily shaded, reduce capacity by 10 percent."
Average ×1.00 quick; ×0.65 on window solar gain Published Neither heavily shaded nor unusually exposed — the ENERGY STAR chart’s own baseline.
Sunny ×1.10 quick; ×0.90 on window solar gain Published ENERGY STAR: "If the room is very sunny, increase capacity by 10 percent."
Strong afternoon sun ×1.18 quick; ×1.00 on window solar gain CalcDomain model Unshaded west or south-west glass taking the full late-afternoon peak. A CalcDomain extension beyond the two ENERGY STAR steps.
Glazing
Single glazing U 1.04 BTU/hr·ft²·°F; SHGC 0.76 CalcDomain model One pane of clear glass. The weakest common assembly by a wide margin.
Double glazing U 0.49 BTU/hr·ft²·°F; SHGC 0.62 CalcDomain model Two panes with an air gap and no coating.
Low-E / high performance U 0.28 BTU/hr·ft²·°F; SHGC 0.31 CalcDomain model Double glazing with a low-emissivity coating and often an inert gas fill, at about the ENERGY STAR Version 7.0 southern-zone U-factor criterion of 0.28.
Triple glazing U 0.2 BTU/hr·ft²·°F; SHGC 0.45 CalcDomain model Three panes, typically coated and gas filled — the lowest heat loss of the four.
Not sure U 0.49 BTU/hr·ft²·°F; SHGC 0.62 CalcDomain model Treated as plain double glazing, which is the most common assembly in existing housing. The page shows this as an assumption, not a fact about your window.
Orientation
North 45 BTU/hr·ft² at SHGC 1.0 CalcDomain model Diffuse sky light only for most of the day.
East 155 BTU/hr·ft² at SHGC 1.0 CalcDomain model Strong morning peak, before the building has warmed up.
South 110 BTU/hr·ft² at SHGC 1.0 CalcDomain model Steady midday gain; a high summer sun strikes south glass at a shallow angle.
West 165 BTU/hr·ft² at SHGC 1.0 CalcDomain model Late-afternoon peak coinciding with the hottest outdoor hour — the worst case for cooling.
Mixed / several directions 115 BTU/hr·ft² at SHGC 1.0 CalcDomain model Glass facing more than one way; an average across the four exposures.
Roof / ceiling
Heated/cooled room above excluded from the envelope CalcDomain model Another conditioned room sits above, so there is no meaningful loss or gain through this ceiling.
Vented attic above ×1.00 on the roof U-factor; +15°F surface temperature in cooling CalcDomain model An unconditioned attic above the ceiling insulation, running hotter than outdoor air on a sunny day.
Insulated roof directly above ×1.00 on the roof U-factor; +5°F surface temperature in cooling CalcDomain model A cathedral or insulated flat roof with the insulation in the roof plane.
Uninsulated roof above U 0.50 absolute (R2.0); +20°F surface temperature in cooling CalcDomain model A roof with no meaningful insulation in it — a garage conversion, a porch roof, an older extension. This is a statement about the roof itself, so it sets the assembly U-factor at about R-2 rather than scaling the insulation grade you chose for the rest of the room.
Exposed flat roof ×2.00 on the roof U-factor; +25°F surface temperature in cooling CalcDomain model A dark flat roof in full sun with the room directly beneath it.
Floor
Heated/cooled room below excluded from the envelope CalcDomain model Another conditioned room sits below, so there is no meaningful loss or gain through this floor.
Unheated space below ×1.00 on the floor U-factor; sees 50% of ΔT CalcDomain model A crawlspace, garage or unheated basement, which tracks about half way between indoors and outdoors.
Slab on ground ×0.60 on the floor U-factor; sees 35% of ΔT CalcDomain model A concrete slab on the ground. Deep ground temperature swings far less than the air.
Exposed to outside air ×1.00 on the floor U-factor; sees 100% of ΔT CalcDomain model A cantilevered floor or a room over an open carport, with outdoor air beneath it.
Air leakage
Tight / new construction 0.35 air changes per hour CalcDomain model Sealed, recently built or deeply retrofitted, usually with mechanical ventilation.
Average 0.7 air changes per hour CalcDomain model An ordinary well-kept house with reasonable weatherstripping.
Drafty / older construction 1.1 air changes per hour CalcDomain model Noticeable draughts at windows and doors; original sashes.
Very drafty 1.6 air changes per hour CalcDomain model Visible gaps, loose sashes or an uninsulated older structure.
Room use
Bedroom ×1.00; default equipment 100 W CalcDomain model Low equipment load and mostly evening occupancy.
Living room ×1.00; default equipment 300 W CalcDomain model Televisions and entertainment equipment, higher peak occupancy.
Office ×1.05; default equipment 400 W CalcDomain model Computers, monitors and lighting running through the hottest part of the day.
Kitchen ×1.00 plus the flat 4,000 BTU/hr kitchen allowance; default equipment 0 W Published Cooking appliances. Carries ENERGY STAR’s flat 4,000 BTU/hr kitchen allowance as a separate line rather than a multiplier.
Open-plan space ×1.05; default equipment 300 W CalcDomain model A large connected space, harder to condition evenly than a closed room of the same area.
Other ×1.00; default equipment 150 W CalcDomain model Anything not covered by the named uses.

Assumptions

Limitations

This calculator provides an estimate for planning and comparison. Building construction, local climate, humidity, ventilation, duct losses and equipment characteristics can all materially change the real HVAC load. For equipment selection in critical or whole-building applications, use an appropriately qualified HVAC professional and a full load calculation.

Sources and review

The two published tables on this page — the ENERGY STAR room air conditioner capacity chart with its four sizing adjustments, and the ENERGY STAR recommended insulation R-values with their 2021 IECC basis — were transcribed cell by cell from the publisher pages and re-read against that markup a second time on 2026-08-19. That is a source-transcription check, NOT an independent third-party engineering review: no outside HVAC engineer has reviewed the load model, and this page does not claim one. Correctness of the arithmetic is enforced by the contract archetype’s golden vectors, the twelve permanent engine fixtures, the metric–imperial equivalence suite, the breakdown reconciliation checks that fail closed rather than print a total its own parts do not add up to, the fail-closed dataset validators proved against deliberately broken fixtures, and the dedicated renderer suite. Every coefficient that is CalcDomain’s own is labelled as a model parameter on the page rather than dressed as a published constant.

Written by Ugo Candido. Last reviewed August 19, 2026. Engine v1.0.0, coefficients v1.0.0, units v1.0.0.